SPS-36 Series Power Supply TECHNICAL SALES BULLETIN

 

HOME

ABOUT ESD

PRODUCTS APP NOTES DOWN LOADS CONTACT ESD LIST PRICE

 

SPS-3.3 24VDC – 3A - Supervised Power Supply/Charger module

SPS-6.5 12VDC – 6A - Supervised Power Supply / Charger module

SPS-3.3E 24VDC module mounted in Enclosure SPS-6.5E 12VDC module mounted SPS-3.3EC8 SPS-3.3 with PDM-8C 8 class II Outputs mounted in Enclosure

SPS-6.5EC8 - SPS-6.5 with PDM-8C 8 class II Outputs mounted in Enclosure

“RT” - Rain Tight NEMA 3 Enclosure

“F” adds Smart Fan inside module for extreme duty

 

Features:

  • Super Clean Linear Performance

  • Universal Input: 85vac–260vac Tolerates
    Brownouts

  • Self Contained No External Transformer Required

  • Precision Battery Charging and Output Regulation.

  • C Models have PDM-8C 8 class II Power Limited
    Outputs with PTC Circuit Breakers  

  • Indicating LED’s for AC, DC Power, and Each
    Output on PDM-8C Board

  • AC Fail Alarm Form C Contacts   

  • Low Battery Alarm Form C Contacts

  • Battery Cut-off Relay Prevents Deep Discharge

  • Battery is Float Charged for Faster Charging with No Switch Over or Drop when AC fails.

  • Thermally Protected

  • Short Circuit Protection

  • Plug-in Battery Cable Assembly is Provided

  • Quality Manufactured in the USA with Lifetime
    Warranty

  • UL and CUL Listed
    UL603 Burglar Alarm System Power Supply
    UL294 Access Control Accessory
    UL1481 & NFPA72 Power Supplies for Fire Systems

  • Compliant with EN 60950, EN61204-3 & FCC A

./F option shown below on a 4 output board

SPS-6.5EC8

SPS-6.5/SPS-3.3 Module

 

     



DESCRIPTION
 

The SPS-3.3 and SPS-6.5 are part of our SPS-36 Series Linear performance power supplies.  They are clean, efficient, heavy duty, low frequency off-line switching power supplies with precision battery charger and power supervision.  These supplies are so clean that they can be used anywhere a linear or switching supply is recommended.  The filtering and switching systems we use are very similar to what you would find on high quality computers.  Even though the SPS-3.3 (24V) and the SPS-6.5 (12V) are both 100 watt power supplies utilizing the same printed wiring board, we offer separate 12V and 24V models for optimum performance.  The universal input of 85vac to 260vac allows them to be used anywhere in the world without adjustments to the power input.  To tolerate brownouts, the SPS-6.5 and SPS-3.3 will remain operational down to 60vac.  The SPS-3.3 and SPS-6.5 are fully self-contained and isolated from the line to all world safety standards.  Each power supply weighs less than 1.5 lbs and occupies less than ½ of a cubic foot of cabinet space.  The SPS-3.3 and SPS-6.5 become an uninterruptible power supply when a stand-by battery(s) is connected with the provided battery cable.  These supplies have a special power limiting circuit that allows the battery(s) to be float charged across the output without lock up or chirping on and off.  The battery(s) is protected with an automatic resetting circuit breaker and diode for over current and accidental reversed battery hookup.  Precision float charging means faster recovery time and longer life for the battery(s).  There is no switch over or voltage drop when input power fails.  Standby battery(s) can be any capacity between 4 and 40 Amp hours.  The SPS-3.3 24VDC is rated for 3 Amps continuous current while the SPS-6.5 12VDC is rated for 6 Amps continuous current.  The SPS-3.3 24VDC has 300ma reserved for battery charging, while the SPS-6.5 has 500ma reserved.  The PDM-8C (C8 option) distribution board adds 8 class II power limited outputs. Power Supervision uses 3 relays and electronics to indicate 3 levels of the stand by battery(s).  The AC FAIL relay is triggered by detecting a small drop in DC output and provides a form C contact set to indicate the AC has failed and the supply is running on standby batteries.  The LOW BAT relay provides a form C contact set to indicate the battery(s) is low.  Either of these form C contacts, can be used to signal a buzzer and/or other signaling device.  A 3rd relay with electronics is used to disconnect the battery(s) at the end of its service limit, preventing deep discharge that can damage the battery(s).  All three relays are normally energized for fail safe operation.

 
  SPECIFICATIONS
 
AC Input: 3P Terminal block in high voltage barrier ....... Line, Neutral, and Earth Ground

AC Input  ........................................................   85-260vac/47-63Hz/150W

Universal AC input does not require any selection switching.

Earth ground terminal must be connected to earth ground.

AC LED Indicator ................................................................ LED Green

AC Line Fuse Link - Inside unit for catastrophic failure.  This fuse is not field replaceable.  A blown fuse would be indicated by the AC LED off with AC power applied.

DC Output: 2P Terminal block 28-12awg

Nominal Voltage SPS-3.3/SPS-6.5 .................................................  24/12vdc

Typical Voltage SPS-3.3/SPS-6.5 ...........................................  27.30/13.65vdc

Total Output continuous SPS-3.3/SPS-6.5 ............................................  3A/6A

SPS-3.3EC8 with PDM-8C Outputs 1-8 Power Limited Class II PTC Circuit Breakers rating. 720mA

SPS-6.5EC8 with PDM-8C- Outputs 1-8 Power Limited Class II PTC circuit breakers rating.1.50A

Typical Output Ripple & Noise SPS-3.3/SPS-6.5
Peak to Peak  .................................................................   50mv/25mv

Current Overload Protection  ..........................................   Electronic & PTC’s

Battery PTC Protection SPS-3.3/SPS-6.5  ............................................   3A/6A

Main Power DC LED adjacent to battery connector......................................... Red

Switching Frequency  ...............................................................   27KHz

Supervisory Functions:

AC Fail Contacts: 3P Terminal block – annunciates AC fail – “C” contacts “NO, O, NC”
 ................................................................................. 2A/120vac

Three position AC fail terminal block is marked “NO, C, NC” are shown in the Normal, energized, AC On condition. Note: AC fail is detected by a slight drop in  DC output voltage.  Relay trip point is approximately 99% battery capacity.

Low battery Output: 3P Terminal block – annunciates Low battery “C” contacts “NO, O, NC”
 ................................................................................  2A/120vac

Low battery trip SPS-3.3/SPS-6.5 ............................................  22.0/11.0 Vdc

AC fail, Low Battery, and Battery cut-off Relays are normally energized for fail-safe operation.

Battery Disconnect trip points 24/12v ........................................... 20.0/10.0

Battery Cutoff internal relay contacts ...............................................  15A

Battery Charging: (Header plug marked [–Bat+])

The battery charger is precision set to float charge 12V or 24V sealed, gel, AGM, or wet lead acid batteries.  Two 12V batteries are connected in series for 24V.  The (AH) Amp hour capacity may be anything between 4AH and 200 AH.  UL evaluated with 40 AH. The Amp Hour recharge rate equals:  
DC Output Amps Rating – DC load Amps + .5

See charge/discharge table on instructions.

Environmental:

Humidity  ..........................................................   95% RH Non Condensing

Ts Storage Temperature  .....................................................   -40oC – 85oC

Ot Operating Temperature Range 100% rating:

     Ot Power module only  ....................................................   -20 – 44oC

     Ot with E-1485 Enclosure on wall  ........................................   -20 – 35oC

     each 5.5% load reduction increases Ot range by  ...............................   +1oC

     “/F” Smart Fan option Increases Ot by:  ........................................   125%

     "/F" Smart Fan turns ON:  ........................................................  35C

Over temp inside (Output dcv is reduced by 1/3) ......................................  71oC

Ot Module with /F option & 50% load  ...........................................   -20- 64oC

Mechanical Characteristics:

SPS-3.3/SPS-6.5 weight (module only)  .............................................  1.5 lbs

SPS-3.3EC8/SPS-6.5EC8 weight in enclosure .........................................  7.6 lbs

SPS-3.3/SPS-6.5 (module only) size: ...........................     6.40H” x 3.95”W x 2.35”D

SPS-3.3/SPS-6.5 module mounting holes center to center (4 holes) ........... 5.36”H x 3.54”W

“E” Enclosure size (inside dimensions).................................  14W” x 9H” x 3.5”D”

“E” Enclosure mounting holes center to center (4 holes)....................   12.74” x 6.98”

Note: For knock out and mounting locations, see graphic drawing of SPS-6.5E on Installation Instructions

 

     

 

 

Approvals:  

EMI conducted and radiated EN61204-3 Class A

UL 294 Access Control, UL 603 Burglar Systems, UL 1076 Proprietary Burglar, UL 1481 Fire Alarm Systems

C603-M1988, ULC C1076, ULC S318 Burglar systems

CSA 22.2 #205 Signal Equipment file # S8102

 

 
pdf SPS-3.3 & SPS6.5 Technical Sales Sheet      pdf SPS-3.3 & SPS6.5 Instruction

Electronic Security Devices Incorporated 09/15/08 jdb
Specifications are subject to change without notice


Electronic Security Devices 
2200 North MacArthur Dr.
Tracy,  CA  95376

 

 E-mail: ESD@SecurityPower.com
   Phone: (209) 229-7140
Fax:  (209) 229-7145