PDD-8PCI DC Power Distribution with Supervised Fire Interface module
Distributed Power Control Interface for Fire, Access, HVAC, Elevator, and Security
 Features:
  • 8 class II Power Limited Outputs with Auto-Resetting
  • Circuit Breakers
  • Each Output is Individually Selectable to
    Turn On, Turn Off, or always On when
    Triggered
  • Outputs can be triggered with:
  1. Voltage or Reverse polarity (opto isolated)
  2. N/O or N/C switch with supervised EOL
  • Form C Contacts (TRIGGERED) and Red LED (TRG)
  • Indicate Trigger Status
  • Form C Contacts (TROUBLE) and Green LED (TRB)
  • Indicate:
  1. One of the output circuit breakers is tripped
  2. Main Fuse Blown or no power on input
  • Universal 11-29VDC Operation
  • Each Output pair has a Removable Terminal Block
  • Each Output has a Green Status LED
  • Main Power has Green Status LED
  • Main Power Pull and Fuse
  • Lifetime Warranty
  • Approvals Pending: UL & ULC 1481, 294, 603 - NFPA72, CSFM & MEA
 
  PDD8PCI
PDD-8PCIDiag
   
 
 
DESCRIPTION
 
 
rubline
HOME rubline
rubline
ABOUT ESD rubline
rubline
CONTACT ESD rubline
rubline
ONLINE CATALOG rubline
rubline
APPLICATION NOTES rubline
rubline
ORDER QUESTIONS rubline
rubline
DOWNLOAD LITERATURE
rubline
rubline
LIST PRICE  & SELECTION GUIDE
rubline
 
The PDD-8PCI power distribution control interface converts a main non-power limited DC power source to 8 class II power-limited outputs that can be controlled by a (FACP) Fire Alarm Control Panel.  Each output can be selectively set (J1-J8) to turn ON or to Turn OFF, Trigger disabled always ON when triggered by the panel.  The FACP or other control system can interface to the PDD-8PCI with either of two or both supervised trigger inputs.  One trigger is activated with a reverse polarity voltage from a FACP.  This trigger is fully isolated with an optical isolator.  The other trigger is an (EOL) 2.2K End Line Resister input which will accept a (N/O) Normally Open switch or a (N/C) Normally Closed switch.
When triggered, the Trigger Transfer Relay removes power from the NORM + buss and transfers it to the TRIG + buss.  Jumpers J1-J8 determine which buss each output is connected to.  The triggered form C contacts also drop off normal when triggered and the Red (TRG) LED turns on.   These contacts can be used to daisy chain other PDD-9ST, latch, or provide feedback to a system.
The Trouble Form C Relay drops off Normal if any one of the PTC circuit breakers is tripped, or main power/fuse is lost.  The Green (TRB) LED is ON during normal operation, It goes off with trouble.  All three relays are Fail-Safe, energized in the normal condition.
Each output has a Green LED that is on when the associated output is ON.
Typical applications for a Fire Alarm System would include adding remote Bells and anunciators, closing dampers, turning off HVAC fans, unlocking fail secure and fail safe doors, and / or returning elevators to first floor.  The installation instructions illustrate these applications.
The PDD-8PCI is available as a module or mounted in an enclosure with any of our DC Power Supplies.

 



SPECIFICATIONS

Input Voltage:                              11–28VDC
Current, Typical, with No Output Load:      90-160mA
Outputs 1–8 continuous duty each:          1.23 Amps
Voltage Trigger:         20% < Input min. 30vdc max.
Voltage Trigger isolation                    Optical
EOL (End of Line) Trigger:        +-50% of 2.2K ohms
Transfer Relay Contacts:                      15Amps
Trouble Form C Contacts:         2A 120vac/1A 220vac
Triggered Form C Contacts:       2A 120vac/1A 220vac



pdf PDD-8PCI Technical Sales Sheet      pdf PDD-8PCI Instructions