Don’t you just hate it when a manufacturer
specifies an unrealistic operating voltage range? I do too!
It’s like saying; if you take this product out of the Lab, it may fail
without warrantee!
Recently
Jay Piper with Security Data & Cable Headquarters had brought to my
attention some cameras that had blown up from too high of
voltage. Even though these cameras were powered by a
competitors 24vac transformer, I must say that in the regard of output
voltage, all transformers are pretty similar. The output AC is a
function of input AC voltage and output loading. In Jay’s case,
the camera manufacturer recommended an input voltage of 24vac +- 10%
(21.6 to 26.4vac). There are some very expensive Ferro resonant
transformers that could meet this specification, but not very practical
and seldom done. If your line voltage is on the outer edges of
normal, your voltage may be out of range for you camera. Let’s
take a look at the numbers to see what would be a practical working
voltage for a 24vac camera.
Nominal
Output at 115vac full rated load ..... 24vac
Zero
load to full load ...................... -0 +3%
AC
Line voltage range around the United States
(105-132vac) .............................. -8% +18%
Normal
Line Losses from wire run
to camera ............................... -10% +0%
Total
Practical Voltage tolerance
in Percentage .......................... -18% +21%
Total
Practical working voltage
for 24vac ...................... 20.0vac – 29.1vac
As
you can see above the practical voltage limits are about 1.6 volts low
and 2.7 volts high. I would recommend checking the voltage at the
camera and if applicable turn heaters and other devices on the
transformer on and off and measure the minimum and maximum voltage.
If your
voltage is below specifications with heater on and normal with the
heater off, then to wire run will have to be shortened or rerun with
larger wire. See application note AN2 24vac wire size table for
further information. If the problem is caused by low line
voltage, contact ESD about a special order step up transformer.
If the
voltage is to high, adding silicon diodes in series with the power can
drop some voltage regardless of load unlike a resistor. Each
silicon diode will drop about .75volts. When using them to drop
AC volts, you must use them in pairs connected in parallel in opposing
directions. Figure 1 shows four 1 Amp diodes connected to drop
1.5vac. Figure two illustrates 2 8 Amp diode bridges connected
together in opposing directions to drop 1.5vac. We rate this at 4
Amps AC without heat sinking.
 |
 |
In
Summary most of the time the line voltage within range to keep your
24ac output within 10%; but always check you voltages and your
specifications to be sure you are in compliance before applying power.
Comments invited! / JDB@SecurityPower.com
Jerry Baker V.P. Engineering
|